Presigo
PDT are differential pressure transmiters with analogue outputs or
communications via EXOline or Modbus.
The Presigo PDT range consists of single or dual port pressure transmitters
with one or two analogue outputs as well as models with two universal inputs
and an RS485 port for communication. The RS485 port can be easily configured
for either EXOline or MODBUS-RTU protocols. Transmitter with an analogue
outputs can be configured for 0-10 V or 4-20 mA output signal.
There are two MEMS dual-chip medical grade sensor modules for general use with
neutral gases. This technology offers very high accuracy and excellent
long-term stability.
The unit can be mounted either vertically or horizontally. If it is installed in a humid environment, vertical mounting is recommended to allow moisture to escape. Two separate cable inlets, a large angled terminal and generous space make wiring easy.
Supply voltage | 24 V AC/DC |
Working temperature | -10...+50 °C |
Accuracy | ⩽ 1 % full scale |
Protection class | IP54 |
Manufacturer | Regin |
Name | Number of sensors | Range | Communication | Output | ||
---|---|---|---|---|---|---|
PDT12 | 1 | 0…1250 Pa | NO | 0…10 V or 4…20 mA | ||
Protection class IP54 operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT25 | 1 | 0…2500 Pa | NO | 0…10 V or 4…20 mA | ||
Protection class IP54 operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT75 | 1 | 0…7500 Pa | NO | 0…10 V or 4…20 mA | ||
Protection class IP54 operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12S25-2 | 2 | PS1: 0…1250 Pa / PS2: 0…2500 Pa | NO | 0…10 V or 4…20 mA | ||
Protection class IP54 operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12S75-2 | 2 | PS1: 0…1250 Pa / PS2: 0…7500 Pa | NO | 0…10 V or 4…20 mA | ||
Protection class IP54 operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12C | 1 | 0…1250 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT25C | 1 | 0…2500 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT75C | 1 | 0…7500 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12C-2 | 2 | PS1: 0…1250 Pa / PS2: 0…1250 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT25C-2 | 2 | PS1: 0…2500 Pa / PS2: 0…2500 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12S25C-2 | 2 | PS1: 0…1250 Pa / PS2: 0…2500 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% | ||||||
PDT12S75C-2 | 2 | PS1: 0…1250 Pa / PS2: 0…7500 Pa | YES | Via EXOline/Modbus | Buy in the store | |
Protection class IP54 communication EXOline/Modbus operating temperature -25…+50˚C overall accuracy pressure ≤ 1% supply voltage 24 V AC/DC ± 15% |