Electric heating controller for controlling electric heating batteries, electric panels etc. It operates on an input signal from an external controller.This is an electric heating controller with triac control for single phase or two phase electric heating. It is connected in series between a power supply and electric heater; such as an electric heating battery or electric panel.
The electric heating controller has a minimum or maximum limitation function which is used when there is a need to regulate the maximum or minimum supply air temperature.
This control accuracy contributes to reduced energy
costs and to the increased comfort of an even temperature. Since the current is
switched by a semiconductor (triac) there are no moving parts that can wear
out. The current is switched at zero crossing, to eliminate network
disturbance.
Protection class | IP20, IP30 |
Working temperature | 0…30°C |
Supply voltage | 230...400 (210 - 415 V ~ 50/60 Hz 16 A) |
Mounting | Wall or DIN-rail |
Analog inputs | 2 NTC |
Analog outputs | Resistive load, max 16 A, min 1 A |
Setpoint | 0...30 °C (the external sensor determines the temperature range) |
Manufacturer | Regin |
Name | Mounting | Supply voltage | ||
---|---|---|---|---|
PULSER-M | Wall | 230…400 (210 - 415 V ~ 50/60 Hz 16 A) | Buy in the store | |
Output load - resistive, max 16 A, min 1A pulse period 60s inputs - external main sensor and external sensor for temperature limitation setpoint range 0…30˚C | ||||
PULSER-ADD | Wall | 230…400 (210 - 415 ~ 50/60 Hz 16 A) | Buy in the store | |
Output load - resistive, max 16 A, min 1A pulse period 60s inputs - external main sensor and external sensor for temperature limitation setpoint range 0…30˚C | ||||
PULSER230X010 | Wall | 230 V AC | Buy in the store | |
Output load - resistive, max 16 A, min 1A pulse period 6/60/120s | ||||
PULSER400X010 | Wall | 400 V AC | Buy in the store | |
Output load - resistive, max 16 A, min 1A pulse period 6/60/120s | ||||
PULSER/D | DIN-rail | 230…400 V (210 -415 V ~ 50/60 Hz 16 A) | Buy in the store | |
Output load - resistive, max 16 A, min 1 A pulse period 60s one input for main sensor setpoint range 0…30˚C | ||||
PULSER-X/D | DIN-rail | 230…400 V (210 -415 V ~ 50/60 Hz 16 A) | Buy in the store | |
Output load - resistive, max 16 A, min 1 A pulse period 6/60/120s input signal - 0...10 V DC |