RDAS7S Damper actuator

RDAS7S Damper actuator

Damper actuator with spring return, 7 Nm

RDAS7S Damper actuator with spring return for 2-point or 0…10V control signal

Spring-return actuators are used in ventilation and air conditioning plants to operate air dampers and air throttles. They can also be used in ventilation sections where the actuator must move to the zero position, i.e. emergency position, during power failure.

When the supply voltage is connected, the actuator moves to a working position corresponding to the control signal (2-point or 0…10 V). On power failure or when the operating voltage is switched off, the spring return moves the actuator to its mechanical zero position.

Main features:

  • Torque 7 Nm
  • Spring return
  • For dampers up to 1.5m2

Technical
data

Protection class IP54
Supply voltage 230 V, 50/60 Hz ; 24 V AC/DC 50/60 Hz
Torque 7 Nm
Mounting Interior
Manufacturer Regin

Standard executions

Name Supply voltage Control signal Auxiliary switch
Więcej RDAS7S-230 230 V, 50/60 Hz 2-point, on/off -
Running time - 60 s Closing time - 15 s Cable length - 0.9 m (max. 300 m)
Więcej RDAS7S-230S 230 V, 50/60 Hz 2-point, on/off Yes
Running time - 60 s Closing time - 15 s Cable length - 0.9 m (max. 300 m)
Więcej RDAS7S-24 24 V AC/DC, 50/60 Hz 2-point, on/off -
Running time - 60 s Closing time - 15 s Cable length - 0.9 m (max. 300 m)
Więcej RDAS7S-24S 24 V AC/DC, 50/60 Hz 2-point, on/off Yes
Running time - 60 s Closing time - 15 s Cable length - 0.9 m (max. 300 m)
Więcej RDAS7S-24A 24 V AC/DC, 50/60 Hz 0…10 V -
Running time - 60 s Closing time - 15 s Cable length - 0.9 m (max. 300 m)