RDAS35 Damper actuator without spring return for 3-point or 0…10 V control signal
The actuators are used in ventilation and air conditioning plants to operate air dampers and air throttles. The actuators can be used for damper areas up to 6.0 m2 and are friction-dependent.
The damper actuators are suitable for modulating controllers (DC 0...10 V) or 3-point controllers, e.g. rotary and linear dampers for air outlets.
When the supply voltage is connected, the actuator moves
to a working position corresponding to the control signal. The position indication
is mechanical and electrical.
Protection class | IP54 |
Supply voltage | 230 V, 50/60 Hz ; 24 V AC/DC 50/60 Hz |
Torque | 35 Nm |
Mounting | Interior |
Manufacturer | Regin |
Name | Supply voltage | Control signal | Auxiliary switch | ||
---|---|---|---|---|---|
RDAS35-230 | 230 V, 50/60 Hz | 3-point, on/off | - | ||
Running time - 125 s Cable length - 0.9 m (max. 300 m) | |||||
RDAS35-24 | 24 V AC/DC, 50/60 Hz | 3-point, on/off | - | ||
Running time - 125 s Cable length - 0.9 m (max. 300 m) | |||||
RDAS35-24A | 24 V AC/DC, 50/60 Hz | 0…10 V | - | ||
Running time - 125 s Cable length - 0.9 m (max. 300 m) |