DTK is a transmitter for measuring differential pressure in liquids and gases. The method of measurement using a ceramic membrane gives a high level of accuracy and stability over a long period.
The transmitter consists of a sensor housing of stainless steel and a ceramic membrane. The construction, incorporating only one moving part and a direct signal from the membrane, offers a high level of accuracy and a short response time. The properties of the membrane also ensure good stability is maintained over time, as well as a low temperature dependency.
Supply voltage | 24 V AC / 18...33 V DC, 0.1 VA ; 11...33 V DC, 0.5 VA |
Working temperature | -15...+80°C |
Protection class | IP65 |
Manufacturer | Regin |
Name | Working range [kPa] | Max. Overload [kPa] | ||
---|---|---|---|---|
DTK10-420 | 0…10 | [60] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK20-420 | 0…20 | [120] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK40-420 | 0…40 | [120] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK100-420 | 0…100 | [500] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK250-420 | 0…250 | [1200] | Buy in the store | |
Accuracy +25°C: ±1.3% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK400-420 | 0…400 | [1200] | Buy in the store | |
Accuracy +25°C: ±0.75% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK600-420 | 0…600 | [1200] | Buy in the store | |
Accuracy +25°C: ±0.4% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK1000-420 | 0…1000 | [2000] | Buy in the store | |
Accuracy +25°C: ±0.4% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK1600-420 | 0…1600 | [3200] | Buy in the store | |
Accuracy +25°C: ±0.4% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 4…20 mA | ||||
DTK10 | 0…10 | [60] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK20 | 0…20 | [120] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK40 | 0…40 | [200] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK100 | 0…100 | [500] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK250 | 0…250 | [1200] | Buy in the store | |
Accuracy +25°C: ±1.25% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK400 | 0…400 | [1200] | Buy in the store | |
Accuracy +25°C: ±0.75% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK600 | 0…600 | [1200] | Buy in the store | |
Accuracy +25°C: ±0.40% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK1000 | 0…1000 | [2000] | Buy in the store | |
Accuracy +25°C: ±0.40% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC | ||||
DTK1600 | 0…1600 | [3200] | Buy in the store | |
Accuracy +25°C: ±0.40% FS Media temperature: –15°C...+80°C Supply voltage [V DC]: 9...32 Output signal: 0…10V DC |